TECHNOLOGY ALL FLOODED AGM GEL Sodium Nickel Chloride (Salt)
Documentation
DownloadsSGL / SGH GroE
Applications and Key Benefits
- Designed for highest reliability in standby mode, for high performance, high
current and deep discharge applications
Ideal for:
• Nuclear and thermal power plants
• Electrical utilities
• Power supply units for substations
• Switchgear
• Signaling and emergency lighting
• IT datacenters
• Starter batteries for diesel generators
- 25 years design life in float operation in temperature controlled environments
- 100% rated capacity throughout the battery life. No requirement to oversize the battery
- Excellent for high current discharge (1 to 60 min), and medium to long
discharge (2 to 8 hours)
- Long life even in the worst operating conditions
- Extra thick pure lead Planté plates
- High reliability post seal
- Extremely long topping-up intervals
- 100% Recyclable
Applicable Standards
- DIN 40738 - specification GroE cells
- IEC 60896 part 11 - vented types requirements & tests
- BS 6290 part 2 - British Standard Planté specification
- UK National Grid (with optional nut & bolt terminals)
FIAMM Manufacturing
- ISO 9001 Quality Management System
- ISO 14001 Environmental Management System
Technical Features
- Positive GroE (Planté) plates, cast from pure lead to avoid capacity drop
during the long battery life
- Negative plates with rugged pasted grid construction with a service life
compatible with the positive plates. The alloy and curing process are designed
to maintain the porosity of the active material during operation
- High purity sulphuric electrolyte with a very low specific gravity of
1.22 ( ±0.01) at 20°C
- Microporous separators maximize electrolyte utilization, minimize resistance
and guarantee lowest self discharge
- Cell containers are injection molded from high quality transparent SAN
(styrene acrylonitrile) for easy cell status inspection
- Lids made of opaque ABS
- Female threaded M10 terminals and pillars with solid brass inserts ensure
highest conductivity and perfect contact
(Optional nut and bolt type terminals with copper inserts)
- High integrity post seal design to avoid electrolyte leakage and terminal corrosion
- Vent plugs effectively return acid spray to the cell under normal operating
conditions of float and boost charging. The vent plugs have a ceramic filter
and bayonet lock, designed to prevent any errant spark or flame from
entering the cell
- Flame retardant lids are optional
- Tin plated solid copper inter-cell connectors are fixed with an insulated screw
with probe hole for electrical measurement
- External recombination plugs optionally available
- < 3% self-discharge per month at 20°C allows 4 months shelf life
- Optional seismic racks UBC zone 4